Daikin Midwall Split Servicing — Gas Leak Detection & Refill in Sandton CBD

Full preventative service: coil clean, filter replacement, drain flush, gas pressure check and electrical torque test. In Sandton CBD this is sandton prime work on midwall split systems, attended within about 35 minutes of dispatch.

On Daikin equipment specifically — inverter splits, vrv multi-storey systems and ducted plant — the faults we see most in Sandton CBD are eev coil sticking on multi-splits and refrigerant loss at flare joints.

Leaks are found before gas goes in: nitrogen pressure test, electronic sniffer and UV dye, then a triple evacuation and a weighed charge.

Building management induction and permit-to-work required for plant rooms. Aircon Repairs & Servicing bookings in Sandton CBD are logged against Block 4 so we can allow for power availability on site.

Typical response window
35 minutes from Sandton
Distance from Sandton CBD
0.4 km
Municipal water hardness
moderate (140 ppm)
Load-shedding schedule
Block 4
Access & compliance
Building management induction and permit-to-work required for plant rooms.
Typical installed systems
Towers on central HVAC and chillers, plus retail and restaurant refrigeration.

Refrigerant data

GasClassificationSuction pressureDischarge pressureTypical use
R410aHFC blend (A1)280-320 kPa at 7 degrees C evaporating2 600-3 000 kPa at 45 degrees C ambientMost inverter splits, ducted systems, VRV/VRF and heat pumps installed since 2005.
R32HFC (A2L, mildly flammable)300-340 kPa at 7 degrees C evaporating2 700-3 100 kPa at 45 degrees C ambientCurrent-generation inverter splits and heat pumps.
R22HCFC (phased out)480-520 kPa at 7 degrees C evaporating1 700-2 000 kPa at 45 degrees C ambientLegacy splits and ducted plant installed before the phase-out.

Common questions

Why is my Daikin unit flashing its indicator light in Sandton CBD?

A flashing operation lamp means the board has logged a fault code. Pressing the cancel button on the remote and holding it cycles the code out; U0 points to a low charge, U4 to a communication fault between indoor and outdoor units, and A5 to a freeze or high pressure trip.

Do you top up gas without finding the leak?

No. A weighed charge into a leaking system is money out the window, so the leak is found and repaired first, then the system is evacuated and charged to the plated weight.

Can you work after trading hours?

Yes. Retail, restaurant and office work is routinely scheduled at night or early morning under a permit-to-work so trading is not interrupted.