Full preventative service: coil clean, filter replacement, drain flush, gas pressure check and electrical torque test. In Sandton CBD this is sandton prime work on midwall split systems, attended within about 35 minutes of dispatch.On Daikin equipment specifically — inverter splits, vrv multi-storey systems and ducted plant — the faults we see most in Sandton CBD are outdoor pcb failure after surge events and eev coil sticking on multi-splits.Every visit starts with a full diagnostic and a written quote before any part is fitted.Building management induction and permit-to-work required for plant rooms. Aircon Repairs & Servicing bookings in Sandton CBD are logged against Block 4 so we can allow for power availability on site.

Typical response window
35 minutes from Sandton
Distance from Sandton CBD
0.4 km
Municipal water hardness
moderate (140 ppm)
Load-shedding schedule
Block 4
Access & compliance
Building management induction and permit-to-work required for plant rooms.
Typical installed systems
Towers on central HVAC and chillers, plus retail and restaurant refrigeration.

Refrigerant data

GasClassificationSuction pressureDischarge pressureTypical use
R410aHFC blend (A1)280-320 kPa at 7 degrees C evaporating2 600-3 000 kPa at 45 degrees C ambientMost inverter splits, ducted systems, VRV/VRF and heat pumps installed since 2005.
R32HFC (A2L, mildly flammable)300-340 kPa at 7 degrees C evaporating2 700-3 100 kPa at 45 degrees C ambientCurrent-generation inverter splits and heat pumps.
R22HCFC (phased out)480-520 kPa at 7 degrees C evaporating1 700-2 000 kPa at 45 degrees C ambientLegacy splits and ducted plant installed before the phase-out.

Common questions

Why is my Daikin unit flashing its indicator light in Sandton CBD?

A flashing operation lamp means the board has logged a fault code. Pressing the cancel button on the remote and holding it cycles the code out; U0 points to a low charge, U4 to a communication fault between indoor and outdoor units, and A5 to a freeze or high pressure trip.

Can you work after trading hours?

Yes. Retail, restaurant and office work is routinely scheduled at night or early morning under a permit-to-work so trading is not interrupted.

Is a compressor replacement guaranteed?

Yes. Replacements are done with a system flush and new drier, and both part and workmanship are warranted, provided the original cause of failure is corrected.

How fast can you get to me?

Emergency callouts are dispatched to the next available technician, with the arrival window confirmed by SMS when the vehicle leaves.

Request a callout or quote

Send it straight to our WhatsApp for the fastest response, or call 069 268 0988 / email info@reyds.co.za.