Full preventative service: coil clean, filter replacement, drain flush, gas pressure check and electrical torque test. In Design Quarter this is luxury gated estates work on midwall split systems, attended within about 60 minutes of dispatch.We work across every major brand installed in Design Quarter, and diagnostics start from the plated design data rather than a guess.A structured cool-down test isolates whether the loss of cooling is airflow, charge, control or compressor related.Tenant and centre coordination for shared plant. Aircon Repairs & Servicing bookings in Design Quarter are logged against Block 12 so we can allow for power availability on site.

Typical response window
60 minutes from Fourways & Northern Suburbs
Distance from Sandton CBD
13 km
Municipal water hardness
hard (185 ppm)
Load-shedding schedule
Block 12
Access & compliance
Tenant and centre coordination for shared plant.
Typical installed systems
Restaurant and showroom cooling.

Refrigerant data

GasClassificationSuction pressureDischarge pressureTypical use
R410aHFC blend (A1)280-320 kPa at 7 degrees C evaporating2 600-3 000 kPa at 45 degrees C ambientMost inverter splits, ducted systems, VRV/VRF and heat pumps installed since 2005.
R32HFC (A2L, mildly flammable)300-340 kPa at 7 degrees C evaporating2 700-3 100 kPa at 45 degrees C ambientCurrent-generation inverter splits and heat pumps.
R22HCFC (phased out)480-520 kPa at 7 degrees C evaporating1 700-2 000 kPa at 45 degrees C ambientLegacy splits and ducted plant installed before the phase-out.

Common questions

Can you work after trading hours?

Yes. Retail, restaurant and office work is routinely scheduled at night or early morning under a permit-to-work so trading is not interrupted.

There is water on the floor under my ice machine, can you find the leak?

We trace it wet rather than guessing: inlet valve weep, split distribution tube, blocked machine drain or a backed-up bin drain all present the same way. The water side is pressure-tested before we recommission.

How urgent is a slow harvest cycle?

Treat it as urgent. A stalling harvest leaves the plate frozen solid, output collapses and the compressor runs against high head pressure, which is how a cheap solenoid fault turns into a compressor replacement.

How fast can you get to me?

Emergency callouts are dispatched to the next available technician, with the arrival window confirmed by SMS when the vehicle leaves.

Request a callout or quote

Send it straight to our WhatsApp for the fastest response, or call 069 268 0988 / email info@reyds.co.za.