Pressure testing, leak detection, vacuum and accurate weighed re-gas of R410a, R32 and legacy R22 systems. In Kyalami this is corporate & commercial work on all split types systems, attended within about 80 minutes of dispatch.We work across every major brand installed in Kyalami, and diagnostics start from the plated design data rather than a guess.Leaks are found before gas goes in: nitrogen pressure test, electronic sniffer and UV dye, then a triple evacuation and a weighed charge.Smallholdings and estates; borehole water common. Aircon Repairs & Servicing bookings in Kyalami are logged against Block 16 so we can allow for power availability on site.
- Typical response window
- 80 minutes from Midrand & Waterfall Corridor
- Distance from Sandton CBD
- 20.4 km
- Municipal water hardness
- hard (205 ppm)
- Load-shedding schedule
- Block 16
- Access & compliance
- Smallholdings and estates; borehole water common.
- Typical installed systems
- Large stands with multiple systems and borehole-fed hot water.
Refrigerant data
| Gas | Classification | Suction pressure | Discharge pressure | Typical use |
|---|---|---|---|---|
| R410a | HFC blend (A1) | 280-320 kPa at 7 degrees C evaporating | 2 600-3 000 kPa at 45 degrees C ambient | Most inverter splits, ducted systems, VRV/VRF and heat pumps installed since 2005. |
| R32 | HFC (A2L, mildly flammable) | 300-340 kPa at 7 degrees C evaporating | 2 700-3 100 kPa at 45 degrees C ambient | Current-generation inverter splits and heat pumps. |
| R22 | HCFC (phased out) | 480-520 kPa at 7 degrees C evaporating | 1 700-2 000 kPa at 45 degrees C ambient | Legacy splits and ducted plant installed before the phase-out. |
Common questions
How often should an aircon need re-gassing?
A correctly installed system should never need gas. If it does, there is a leak, so we pressure test and repair the leak before charging rather than topping up annually.
Do you top up gas without finding the leak?
No. A weighed charge into a leaking system is money out the window, so the leak is found and repaired first, then the system is evacuated and charged to the plated weight.
Do you charge a callout fee?
A standard callout and diagnostic fee applies and is quoted upfront. It is credited against the repair when you accept the quote.
Request a callout or quote
Send it straight to our WhatsApp for the fastest response, or call 069 268 0988 / email info@reyds.co.za.