Pressure testing, leak detection, vacuum and accurate weighed re-gas of R410a, R32 and legacy R22 systems. In Melrose Arch this is sandton prime work on all split types systems, attended within about 40 minutes of dispatch.On York equipment specifically — commercial ducted, chillers and large air handling plant — the faults we see most in Melrose Arch are condenser fan contactor welding and low charge causing high superheat.Every visit starts with a full diagnostic and a written quote before any part is fitted.Precinct management controls contractor access and lift bookings. Aircon Repairs & Servicing bookings in Melrose Arch are logged against Block 6 so we can allow for power availability on site.

Typical response window
40 minutes from Sandton
Distance from Sandton CBD
4.9 km
Municipal water hardness
moderate (135 ppm)
Load-shedding schedule
Block 6
Access & compliance
Precinct management controls contractor access and lift bookings.
Typical installed systems
High-density mixed use: VRV/VRF, restaurant refrigeration and coldrooms.

Refrigerant data

GasClassificationSuction pressureDischarge pressureTypical use
R410aHFC blend (A1)280-320 kPa at 7 degrees C evaporating2 600-3 000 kPa at 45 degrees C ambientMost inverter splits, ducted systems, VRV/VRF and heat pumps installed since 2005.
R32HFC (A2L, mildly flammable)300-340 kPa at 7 degrees C evaporating2 700-3 100 kPa at 45 degrees C ambientCurrent-generation inverter splits and heat pumps.
R22HCFC (phased out)480-520 kPa at 7 degrees C evaporating1 700-2 000 kPa at 45 degrees C ambientLegacy splits and ducted plant installed before the phase-out.

Common questions

How often should an aircon need re-gassing?

A correctly installed system should never need gas. If it does, there is a leak, so we pressure test and repair the leak before charging rather than topping up annually.

Can you work after trading hours?

Yes. Retail, restaurant and office work is routinely scheduled at night or early morning under a permit-to-work so trading is not interrupted.

Do you top up gas without finding the leak?

No. A weighed charge into a leaking system is money out the window, so the leak is found and repaired first, then the system is evacuated and charged to the plated weight.

What does an annual service contract include?

Scheduled visits, priority response between visits, a written condition report per unit and fixed labour rates for the contract year.

Request a callout or quote

Send it straight to our WhatsApp for the fastest response, or call 069 268 0988 / email info@reyds.co.za.