Daikin Ducted Central HVAC Repair — Gas Leak Detection & Refill in Rosebank

Repairs to ducted central plant: fan coils, dampers, ducting leaks, thermostats and condensing units. In Rosebank this is upper residential work on ducted central systems, attended within about 45 minutes of dispatch.

On Daikin equipment specifically — inverter splits, vrv multi-storey systems and ducted plant — the faults we see most in Rosebank are refrigerant loss at flare joints and outdoor pcb failure after surge events.

Leaks are found before gas goes in: nitrogen pressure test, electronic sniffer and UV dye, then a triple evacuation and a weighed charge.

Building management access and lift bookings for plant. Aircon Repairs & Servicing bookings in Rosebank are logged against Block 6 so we can allow for power availability on site.

Typical response window
45 minutes from Rosebank & Parks Belt
Distance from Sandton CBD
6.4 km
Municipal water hardness
moderate (135 ppm)
Load-shedding schedule
Block 6
Access & compliance
Building management access and lift bookings for plant.
Typical installed systems
Offices, hotels and restaurants on VRF and central plant with heavy refrigeration load.

Refrigerant data

GasClassificationSuction pressureDischarge pressureTypical use
R410aHFC blend (A1)280-320 kPa at 7 degrees C evaporating2 600-3 000 kPa at 45 degrees C ambientMost inverter splits, ducted systems, VRV/VRF and heat pumps installed since 2005.
R32HFC (A2L, mildly flammable)300-340 kPa at 7 degrees C evaporating2 700-3 100 kPa at 45 degrees C ambientCurrent-generation inverter splits and heat pumps.

Common questions

Why is my Daikin unit flashing its indicator light in Rosebank?

A flashing operation lamp means the board has logged a fault code. Pressing the cancel button on the remote and holding it cycles the code out; U0 points to a low charge, U4 to a communication fault between indoor and outdoor units, and A5 to a freeze or high pressure trip.

Do you top up gas without finding the leak?

No. A weighed charge into a leaking system is money out the window, so the leak is found and repaired first, then the system is evacuated and charged to the plated weight.

Can you work after trading hours?

Yes. Retail, restaurant and office work is routinely scheduled at night or early morning under a permit-to-work so trading is not interrupted.

Related jobs nearby

Request a callout or quote

Send it straight to our WhatsApp for the fastest response, or call 012 546 6670 / email info@reyds.co.za.