Board-level diagnostics and repair of inverter midwall and multi-split systems that trip, short-cycle or stop cooling. In Sunninghill Office Park this is luxury gated estates work on inverter split systems, attended within about 55 minutes of dispatch.On Daikin equipment specifically — inverter splits, vrv multi-storey systems and ducted plant — the faults we see most in Sunninghill Office Park are outdoor pcb failure after surge events and eev coil sticking on multi-splits.Every visit starts with a full diagnostic and a written quote before any part is fitted.Park reception sign-in. Aircon Repairs & Servicing bookings in Sunninghill Office Park are logged against Block 11 so we can allow for power availability on site.

Typical response window
55 minutes from Fourways & Northern Suburbs
Distance from Sandton CBD
9.9 km
Municipal water hardness
moderate (165 ppm)
Load-shedding schedule
Block 11
Access & compliance
Park reception sign-in.
Typical installed systems
Corporate ducted HVAC and kitchenette refrigeration.

Refrigerant data

GasClassificationSuction pressureDischarge pressureTypical use
R410aHFC blend (A1)280-320 kPa at 7 degrees C evaporating2 600-3 000 kPa at 45 degrees C ambientMost inverter splits, ducted systems, VRV/VRF and heat pumps installed since 2005.
R32HFC (A2L, mildly flammable)300-340 kPa at 7 degrees C evaporating2 700-3 100 kPa at 45 degrees C ambientCurrent-generation inverter splits and heat pumps.

Common questions

Why is my Daikin unit flashing its indicator light in Sunninghill Office Park?

A flashing operation lamp means the board has logged a fault code. Pressing the cancel button on the remote and holding it cycles the code out; U0 points to a low charge, U4 to a communication fault between indoor and outdoor units, and A5 to a freeze or high pressure trip.

Can you work after trading hours?

Yes. Retail, restaurant and office work is routinely scheduled at night or early morning under a permit-to-work so trading is not interrupted.

Do you top up gas without finding the leak?

No. A weighed charge into a leaking system is money out the window, so the leak is found and repaired first, then the system is evacuated and charged to the plated weight.

What does an annual service contract include?

Scheduled visits, priority response between visits, a written condition report per unit and fixed labour rates for the contract year.

Request a callout or quote

Send it straight to our WhatsApp for the fastest response, or call 069 268 0988 / email info@reyds.co.za.