Pressure testing, leak detection, vacuum and accurate weighed re-gas of R410a, R32 and legacy R22 systems. In Blair Atholl this is luxury gated estates work on all split types systems, attended within about 85 minutes of dispatch.We work across every major brand installed in Blair Atholl, and diagnostics start from the plated design data rather than a guess.Leaks are found before gas goes in: nitrogen pressure test, electronic sniffer and UV dye, then a triple evacuation and a weighed charge.Gated golf estate with contractor accreditation and limited daily entry slots. Aircon Repairs & Servicing bookings in Blair Atholl are logged against Block 14 so we can allow for power availability on site.

Typical response window
85 minutes from Fourways & Northern Suburbs
Distance from Sandton CBD
24 km
Municipal water hardness
hard (215 ppm)
Load-shedding schedule
Block 14
Access & compliance
Gated golf estate with contractor accreditation and limited daily entry slots.
Typical installed systems
Very large homes on ducted plant with pool and hot water heat pumps.

Refrigerant data

GasClassificationSuction pressureDischarge pressureTypical use
R410aHFC blend (A1)280-320 kPa at 7 degrees C evaporating2 600-3 000 kPa at 45 degrees C ambientMost inverter splits, ducted systems, VRV/VRF and heat pumps installed since 2005.
R32HFC (A2L, mildly flammable)300-340 kPa at 7 degrees C evaporating2 700-3 100 kPa at 45 degrees C ambientCurrent-generation inverter splits and heat pumps.
R22HCFC (phased out)480-520 kPa at 7 degrees C evaporating1 700-2 000 kPa at 45 degrees C ambientLegacy splits and ducted plant installed before the phase-out.

Common questions

How often should an aircon need re-gassing?

A correctly installed system should never need gas. If it does, there is a leak, so we pressure test and repair the leak before charging rather than topping up annually.

Do you top up gas without finding the leak?

No. A weighed charge into a leaking system is money out the window, so the leak is found and repaired first, then the system is evacuated and charged to the plated weight.

Do you work inside gated estates?

Regularly. Technician details, ID numbers and vehicle registration are submitted to the HOA or gatehouse before the appointment so access is cleared in advance.

Request a callout or quote

Send it straight to our WhatsApp for the fastest response, or call 069 268 0988 / email info@reyds.co.za.